UPS-PC-652A

Question
UPS switches off automatically after a very short time, but the battery indicator still shows (almost) full battery.
Answer
Every UPS has a certain maximum power output (W), but also a minimum required load. In order to work correclty, the connected load should be at least 5% of the maximum capacity of the UPS. For example, a 700 W UPS needs at least a connected load of 35 W to work. Otherwise it will shut itself down automatically as a safety measure to preserve the batteries. Also when the connected load is higher than the maximum capacity of the UPS, the device will shut down.

UPS-PC-1202AP

Question
UPS switches off automatically after a very short time, but the battery indicator still shows (almost) full battery.
Answer
Every UPS has a certain maximum power output (W), but also a minimum required load. In order to work correclty, the connected load should be at least 5% of the maximum capacity of the UPS. For example, a 700 W UPS needs at least a connected load of 35 W to work. Otherwise it will shut itself down automatically as a safety measure to preserve the batteries. Also when the connected load is higher than the maximum capacity of the UPS, the device will shut down.

UPS-PC-850AP

Question
UPS switches off automatically after a very short time, but the battery indicator still shows (almost) full battery.
Answer
Every UPS has a certain maximum power output (W), but also a minimum required load. In order to work correclty, the connected load should be at least 5% of the maximum capacity of the UPS. For example, a 700 W UPS needs at least a connected load of 35 W to work. Otherwise it will shut itself down automatically as a safety measure to preserve the batteries. Also when the connected load is higher than the maximum capacity of the UPS, the device will shut down. Question
UPS switches off automatically after a very short time, but the battery indicator still shows (almost) full battery.
Answer
Every UPS has a certain maximum power output (W), but also a minimum required load. In order to work correclty, the connected load should be at least 5% of the maximum capacity of the UPS. For example, a 700 W UPS needs at least a connected load of 35 W to work. Otherwise it will shut itself down automatically as a safety measure to preserve the batteries. Also when the connected load is higher than the maximum capacity of the UPS, the device will shut down.